National Manufacturers informed their national association about their CE-marked products NSHEV. EUROLUX collected these information and published it in the following list.
A contact to the national association or to the manufacturers is very simple,please use the link shown in the list.

For installation at site it is very important to know that the NSHEV is certificated for the special building situation (e.g.: assembly  in walls or roofs, slope of the roof, necessary class for wind- or snow-loads, tested situation of the aerodynamic free area).

The certificated approximation is described in the certification report and in EN 12101-2.

PDF-Download: CE-marked NSHEV

CE-certification according EN 12101-2

When today building products with a CE marking are brought into market, they must apply the requirements of the relevant harmonized European standards – and have to be certified.

In case of natural smoke and heat ventilation systems (NSHEVS) the national regulations determine that the accordance with EN 12101-2 is required (declaration of conformity). Conformance has to be prove by certification. This consists of an initial type test (ITT) and a factory owned production control (FPC). Annex ZA of the standard contains exact data which characteristics of NSHEVS are to be tested in the certification procedure.

Initial Type Test (ITT)
For initial type test partial tests have to be carried out in the following order for CE certification:

1. Determination of aerodynamic free area
2. Test of reliability
3. Test for opening under load (snow load)
4. Test for low ambient temperature
5. Test of stability against wind load
6. Test of heat exposure

Test 2:
Reliability

(Re)

Test 3:
Opening under load
(SL)

Test 4:
Low ambient temperature
(T)

Test 5:
Wind load

(WL)

Test 6:
Heat exposure

(B)

Classes according EN 12101-2

Re A*

SL A*

T A*

WL A*

B A*

Re 50

SL 0

T 0 °C

WL 1.500

B 300

Re 1.000

SL 125

T -5 °C

WL 3.000

B 600

SL 250

T -15 °C

SL 500

T -25 °C

SL 1.000

*)  The value of A can be selected to meet specific requirements

Table 1: Overview of classes according EN 12101-2

Every partial test must be documented in a test report. An initial type test also has to be carried out always, when changes on the NSHEVS influence the characteristics essentially.

Factory Production Control (FPC)
Factory owned production control has to be carried out, documented and maintained by the manufacturer or distributor. It has to be so extensive that conformity of the product is apparent and can be controlled, proved and evaluated by neutral test bodies regularly. It is sufficient for example to operate a factory owned production control according to EN ISO 9001.

 

Level of safety
In the single member states of the EC rule different legal regulations, that mirror in a individual level of safety:

Member state

Test 2 / Re

Test 3 / SL

Test 4/
T

Test 5 /
WL

Test 6 /
B

Belgium Stairhouses:



Industrial buildings:

50

125

-15 °C

Middle of the roof:1500

B 300

Edge of the roof: 3000

-

-

-

-

-

Germany

-

-

-

-

B 300

France

300

250

0 °C

1500

B 300

Italy

-

-

-

-

B 300

Netherlands

-

-

-

-

-

Austria
Stairhouses
(*TRVB S 111):

Industrial buildings up to 1.200 m² floor area (*OIB):

Industrial buildings above 1.200 m² floor area
(*TRVB S 111) :

-

 

500

-

-

-

-

 

25 % of local snow load, min. 500

-

-

B 300

-

 

25 % of local snow load, min. 500

-

-

B 300

Finland
Stairhouses:
Industrial buildings:

50

500

0 °C

Middle of the roof:1500

B 300 **)

Edge of the roof: 3000

* TRVB: technical guidelines preventive fire protection
* OIB: Austrian Institute of Construction Engineering

**)B 600 for:
- automatically operated ventilators in design to resist full flush
- manually operated ventilators
- Ventilators with delayed release, for example because of sprinkler system

Table 2: Legal minimum requirements for the test classes according to member states

To uphold the reached level of safety in the member states the national head organisations propose as a minimum to claim the test classes for NSHEVS according EN 12101-2 listed in table 3:

Member state

Test 2 / RE

Test 3 / SL

Test 4/
T

Test 5 /
WL

Test 6 /
B

Belgium Stairhouses:



Industrial buildings:

50

125

-15 °C

Middle of the roof:1500

B 300

Edge of the roof: 3000

50

250

-5 °C

1500

B 300

Germany

50

500

-5 °C

1500

B 300

France

300

250

0 °C

1500

B 300

Italy

50

500

0 °C

1500

B 300

Netherlands

50

500

-5 °C

1500

B 300

Austria
Stairhouses:


Industrial buildings:

50

 

25 % of local snowload, min. 500

0 °C / - 15 °C

1500

B 300

50

 

25 % of local snowload, min. 500

0 °C / - 15 °C

1500

B 300

Finland

50

500

0 °C

Middle of the roof:1500

B 300

Edge of the roof: 3000

Table 3: Proposal of the national head organisations for complying minimum threshold values

PDF-Download: VdS 2815en Interaction of water extinguishing systems and smoke and heat extractors

 