For installation at site it is very important to know that the NSHEV is certificated for the special building situation (e.g.: assembly in walls or roofs, slope of the roof, necessary class for wind- or snow-loads, tested situation of the aerodynamic free area).
The certificated approximation is described in the certification report and in EN 12101-2.
CE-certification according EN 12101-2
When today building products with a CE marking are brought into market, they must apply the requirements of the relevant harmonized European standards – and have to be certified.
In case of natural smoke and heat ventilation systems (NSHEVS) the national regulations determine that the accordance with EN 12101-2 is required (declaration of conformity). Conformance has to be prove by certification. This consists of an initial type test (ITT) and a factory owned production control (FPC). Annex ZA of the standard contains exact data which characteristics of NSHEVS are to be tested in the certification procedure.
Initial Type Test (ITT)
For initial type test partial tests have to be carried out in the following order for CE certification:
1. Determination of aerodynamic free area
2. Test of reliability
3. Test for opening under load (snow load)
4. Test for low ambient temperature
5. Test of stability against wind load
6. Test of heat exposure
Test 2: |
Test 3: |
Test 4: |
Test 5: |
Test 6: |
Classes according EN 12101-2 |
||||
Re A* |
SL A* |
T A* |
WL A* |
B A* |
Re 50 |
SL 0 |
T 0 °C |
WL 1.500 |
B 300 |
Re 1.000 |
SL 125 |
T -5 °C |
WL 3.000 |
B 600 |
SL 250 |
T -15 °C |
|||
SL 500 |
T -25 °C |
|||
SL 1.000 |
||||
*) The value of A can be selected to meet specific requirements
Table 1: Overview of classes according EN 12101-2
Every partial test must be documented in a test report. An initial type test also has to be carried out always, when changes on the NSHEVS influence the characteristics essentially.
Factory Production Control (FPC)
Factory owned production control has to be carried out, documented and maintained by the manufacturer or distributor. It has to be so extensive that conformity of the product is apparent and can be controlled, proved and evaluated by neutral test bodies regularly. It is sufficient for example to operate a factory owned production control according to EN ISO 9001.
Level of safety
In the single member states of the EC rule different legal regulations, that mirror in a individual level of safety:
Member state |
Test 2 / Re |
Test 3 / SL |
Test 4/ |
Test 5 / |
Test 6 / |
Belgium Stairhouses: Industrial buildings: |
50 |
125 |
-15 °C |
Middle of the roof:1500 |
B 300 |
Edge of the roof: 3000 |
|||||
- |
- |
- |
- |
- |
|
Germany |
- |
- |
- |
- |
B 300 |
France |
300 |
250 |
0 °C |
1500 |
B 300 |
Italy |
|
|
|
|
|
Netherlands |
|
|
|
|
|
Austria |
|
|
|
|
|
Table 2: Legal minimum requirements for the test classes according to member states
To uphold the reached level of safety in the member states the national head organisations propose as a minimum to claim the test classes for NSHEVS according EN 12101-2 listed in table 3:
| Member state | Test 2 / RE |
Test 3 / SL |
Test 4/ |
Test 5 / |
Test 6 / |
Belgium Stairhouses: Industrial buildings: |
50 |
125 |
-15 °C |
Middle of the roof:1500 |
B 300 |
Edge of the roof: 3000 |
|||||
50 |
250 |
-5 °C |
1500 |
B 300 |
|
Germany |
50 |
500 |
-5 °C |
1500 |
B 300 |
France |
300 |
250 |
0 °C |
1500 |
B 300 |
Italy |
|
|
|
|
|
Netherlands |
|
|
|
|
|
Austria |
|
|
|
|
|
Table 3: Proposal of the national head organisations for complying minimum threshold values
PDF-Download: VdS 2815en Interaction of water extinguishing systems and smoke and heat extractors